Tuba Installation Guide Technical Specifications
MAN-TUBIG (Ver. 1.502)
www.elmomc.com
73
4.10. I/Os
The Tuba has:
10 Digital Inputs
6 Digital Outputs
2 Analog Inputs
4.10.1. Digital Input Interfaces (on the GENERAL I/O port)
Feature Details Connector Location
Type of input
Optically isolated
Single ended
PLC level
Input current
=
2500
5.6 VVin
Iin
* Iin = 2.2 mA @ Vin = 12 V
Input current
for high speed
inputs 5 & 6
=
1250
5.6 VVin
Iin
* Iin = 4.4 mA @ Vin = 12 V
High-level input
voltage
12 V < Vin < 30 V, 24 V typical
Low-level input
voltage
0 V < Vin < 6.5 V
Minimum pulse
width
> 4 x TS, where TS is sampling time
Execution time
(all inputs):
the time from
application of
voltage on input
until execution
is complete
If input is set to one of the built-in functions Home, Inhibit, Hard Stop,
Soft Stop, Hard and Soft Stop, Forward Limit, Reverse Limit or Begin
execution is immediate upon detection:
0 < T < 4 x TS
If input is set to General input, execution depends on program. Typical
execution time: 0.5 msec.
In
p
u
t R
e
tu
r
n
(
i)
DIGINPUT
Rin = 2.5K Vz = 5.1 V
Digital Input Schematic
DIGITAL INPUTS
Vista de pagina 72