Elmomc SimplIQ Digital Servo Drives-Bell Command Referenc Manual de usuario Pagina 263

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 315
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 262
The PDO does not specify the QP vector elements to be programmed; instead, a write
pointer specifies them. The parameter MP[6] sets the value of the write pointer, which
may be set once for the entire motion. The write pointer is incremented automatically by
2 each time the drive receives a new PT motion-programming message. The CANopen
auto-increment mode is described in the following flowchart:
Motion
segment
completed
?
N >= MP[2]-1
Increment
read pointer
Read the read pointer to the
QP vector and calculate the
parameters of the next motion
segment
Initial
conditions:
PT read
pointer equals
N
Interpolate
position
command
Go to
position
controller
Exit PT mode:
Set Stop motion,
using the SD
deceleration
Set the read
pointer to
MP[1]
Yes
No
No
EMERGENCY:
QUEUE
UNDERFLOW
MP[4]>0 and
(Write pointer ==
N+1 or
left time < MP[4])
EMERGENCY:
QUEUE LOW
Yes
No
Read pointer ==
Write pointer
Yes
Yes
Figure 6-9: PT Auto-increment Mode Flowchart
This flow differs from the basic mode because:
The read pointer reaching the write pointer identifies motion queue underflow.
Emergency objects are issued for the queue low and queue underflow events.
d. Programming Sequence for Auto-increment PVT Mode
SimplIQ for Steppers Application Note The Position Reference Generator
MAN-STECR (Ver. 1.1)
64
Vista de pagina 262
1 2 ... 258 259 260 261 262 263 264 265 266 267 268 ... 314 315

Comentarios a estos manuales

Sin comentarios